888-878-5480

Salisbury Concentric Neutral Ground Clamp With 4' Cable 7603C-ES


The concentric neutral jumper Assembly is used for bonding purposes onnon-jacketed cable. It is usually installed across a portion of cable to be cut, repaired or spliced. The assembly is left in place until the concentric neutral is spliced. As a safety precaution, follow all of your organization’s applicable rules and/or policies pertaining to faulted cable, spiking and grounding.
Made with two ground clamps and 4 ft (1.22 m) of 1/0 clear jacketed extra flexible copper cable, the concentric neutral ground clamp is spring pressured. The assemblies have a continuous current rating of 250 amps and fault rated to ASTM Grade 1, 14 KA for 15 cycles. Other lengths are available. Bag not included.
The components of the underground dead break ground set provide safe and simple grounding methods on padmount transformers or any related UR D equipment. These grounds can be ordered in complete sets or individual components. The jumpers are made with 6 ft (1.83m) lengths of #2, clear-jacketed, extra flexible cable. Clamps (7640001E) supplied include an eye for a grip-all insulating stick application.
The URD Grounding Assembly is used for underground personal protective grounding elbow used for grounding pad-mounted equipment, switches and transformers when performing de-energized maintenance on UR D distribution systems, and draining DC capacitive charges from de-energized UR D cables.
Dominion Energy #99236800